Module ups 90kw~210kw
Module ups 90kw~210kw

Offering high efficiency and overload capability, it is a truly modular UPS system which can easily scales in 30kW increments up to 210kW. Modular design is applied in power module, STS module and battery module. It will simplify maintenance and replaceme

Scudo 400VA/600VA Standby UPS
Scudo 400VA/600VA Standby UPS
Scudo 400VA/600VA Standby UPS
  • High efficiency online double conversion technology

  • High scalability

  • Unity output power factor

  • Modular design lowers MTTR

  • N+1 or N+X parallel redundancy for power guarantee

  • Ease of installation and maintenance

  • Flexible battery configuration adapts different applications

  • Adjustable charging current

  • High overload capability


Model+Power 30U-90+Power 42U-120+Power 30U-120+Power 30U-180+Power 42U-210
TYPEStandard SeriesExtended Series
PHASE3-phase in/3-phase out
MAX. TOTAL CAPACITY 90 KW120 KW120 KW180 KW210 KW
MAX. UPS POWER MODULES34468
TOPOLOGYTrue Double-Conversion Online
INPUT
Nominal Voltage3 x 400 VAC (3Ph+N)
Voltage Range305 ~ 477 VAC @Full load; 208 ~ 304VAC@ <70% Load
Nominal Frequency50/60Hz (Auto Sensing)
Frequency Range40Hz ~70Hz
Power Factor> 0.99 @ 100% Load , >0.98 @ 50% Load

Harmonic Distortion

 (THDi)

< 3% @ 100% load
OUTPUT
Nominal Voltage3 x 400 VAC (3Ph+N)

Voltage Regulation 

(Steady state)

≤ ± 1% Typical (balanced load) ; ≤ ± 2% Typical (unbalanced load)

Voltage Regulation 

(Transient)

≤ ± 5% Typical
Nominal Frequency50/60Hz

Frequency Range 

(Synchronized)

46Hz ~ 54Hz or 56Hz ~ 64Hz
Overload Capability1 hour for 110%, 10 mins for 120%,; 1 min for 150%, 200ms for >150%
Harmonic Distortion≥1.5% THD (Linear Load) ; ≤ 4% THD (Non-linear Load
EfficiencyUp to 94.5%
BATTERY / CHARGER
Nominal Voltage+/- 216V (12V x 36 pcs)
Maximum Voltage+/- 240V (12V x 40 pcs)
Minimum Voltage+/- 192V (12V x 32 pcs)
Float Charging Voltage2.25V / Cell
Boost Charging Voltage2.35V / Cell
Temperature CompensationYes
Maximum Charging Current8A (User-adjustable)
PHYSICAL

Cabinet Dimension 

(D x W x H) mm

1100*600*14851100*600*20301100*600*14851100*600*14851100*600*2030
ENVIRONMENT
Operating Temperature0 ~ 40°C
Relative Humidity0 ~ 95% non-condensing
Altitude<1000m for Nominal power
IP ClassIP 20
MANAGEMENT
Smart RS-232/USB

Supports Windows 2000/2003/XP/Vista/2008, Windows 7/8, Linux, Unix and MAC

Optional SNMPPower management from SNMP manager and web browser
STANDARDS
SafetyIEC/EN 60950-1; IEC/EN 62040-1
EMCIEC/EN 62040-2 Category C3