GL 33 10KVA-200KVA
GL 33 10KVA-200KVA

Embedded with isolation transformer, Giant series will eliminates common mode noise and the need to install expensive dedicated circuits. It provides reliable galvanically isolated power to critical equipment.

Scudo 400VA/600VA Standby UPS
Scudo 400VA/600VA Standby UPS
Scudo 400VA/600VA Standby UPS

o  Advanced DSP digital control technology

o  Large-screen LCD + LED in Chinese and      English display

o  Dual AC input

o  Parallel machine functions

o  High loading capacity, shock stronger

o  Charging current settable

o  Intelligent battery management

o  Adaptive system frequency and phase sequence

o  Protection and alarming functions

o  Especially for banks, telecom, government,      transportation, manufacturing, education, sensitive devices, etc.


MODEL

(3 Phase Input
  /3 Phase Output)

GL33

  10K

GL33

  20K

GL33

  30K

GL33

     40K

GL33

   60K

GL33

   80K

GL33

   100K

GL33

 120K

GL33

   160K

GL33 

  200K

Input

Mains

Rated Voltage

380V(Line Voltage)

Rated Voltage

& Range

380V±25%

Frequency

& Range

46Hz-54Hz, 56Hz-64Hz

Bypass Input

Rated Voltage

380V(Line Voltage)

Rated Voltage

& Range

380V±25%

Frequency

& Range

46Hz-54Hz, 56Hz-64Hz

Output

Rated Power

10KVA
/8KW

20KVA
 /16KW

30KVA
 /24KW

40KVA
/32KW

60KVA
/48KW

80KVA
 /64KW

100KVA
/80KW

120KVA
/96KW

160KVA
 /128KW

200KVA/160KW

Rated Voltage

380V(Line Voltage)

Rated Voltage

& Stability

380V±2%

THDV

Linear  Load

≤3%

Non-linear Load

≤8%

Output Power factor

0.8(Lag)

Tracking Fruquency 
  & Range

46Hz-54Hz, 56Hz-64Hz

Fruquency & Stability

    (Battery

    Inverter)

(50±0.1)Hz, (60±0.1)Hz

Overload
  Capability

Less than 105%±5% for overload alarm;
  105%±5%~125%±5% for 2 minutes;
  125%±5%~150%±5% for 30 second;
  More than 150%±5% for 0.5 second;

Converting time
  (Normal Mode)

<1mS

Converting time
  (ECO Mode)

<25mS

System

System Efficiency
  (Linear Load)

≥76%

≥82%

≥85%

≥89%

≥90%

Display

LCD+LED

EMS
/EMI

Transmission

IEC EN62040-02

Radiation

Resisting   Interference

IEC 61000-4-2.4.5 Level IV, IEC61000-4-3 Level III

Safety 
  Requirements

GB4943-2001/IEC62040-1

Noise Level
  (1M)

≤55dB

≤70dB

Isolate Impedance
  (Ω)

>2M(500VDC)

Surge Current
   Protection

IEC60664-1 IV

Environment

Operating 
  Temperature

0℃ - 40℃

Elevation

<1000m

Storing 
  Temperature

-15℃ - 45℃

Operation 
  Humidity

20% - 95%

Battery

192VDC

384VDC

UPS Size(W x H x D)mm

455x1045x830

515x1135x830

700x1600x800

850x1600x800

1300x1900x900

Package Size(WxHxD)mm

525x1250x925

575x1305x915

765x1777x870

920x1777x870

1380x2055x986

 Product specifications are subject to change without notice